Tips: Assure you are using the proper wire for the type of thermocouple you are using.

Type ---Make-up  Approx Range -US Color Code

B

 

Platinum/Rhodium (+) Platinum around 30 %

Platinum/ Rhodium (-) usually around 5%

 2500 -3100F 1370-1700C

+ Gray

- Red

C

 

 Tungsten /Rhenium (+) tungsten around 5%

 Tungsten /Rhenium (-) tungsten around 25%

 3000-4200F 1650-2315C

+ Varies

-Red

 E

 

Chromel (+)

Constantan (-)

200-1650F 95-900C

 

+ Black

- Red

J

 

 Iron (+)

Constantan (-)

200-1400F 95-760C

 

+ White

- Red

 K

 

 Chromel (+)

 Alumel (-)

200-2300F 95-1260C

+ Yellow

-Red

N

 

Nicrosil (+)

Nisil (-)

1200-2300F 650-1260C

+ usually black

- Red

R

 

Platinum/Rhodium (+)

Platinum (-)

1600-2640F 870-1450C

+ Black

- Red

S

 

Platinum 10% Rhodium (+)

Platinum (-)

1800-2640F 980-1450C

+ Black

- Red

T

 

Copper (+)

Constantan (-)

 -330-660F -200-350C

+ Blue

-Red

*Tenn Tech Automation Controls bears no responsibilities associated with the use of the information on this page. Information is believed to be correct but is not warranted.

 